Measurement methods
- Impulse method – measurement of lightning protection systems with a measuring impulse ramp of 4/10 μs, 8/20 μs, 10/350 μs
- 3-pole and 4-wire method – measurement of earthing systems using auxiliary probes
- 3-pole method with clamp – measurement of earthing systems with multiple earth electrodes
- Two-clamp method – measurement of earthing system when the auxiliary probes cannot be used
- Earth resistivity – Wenner method
- Resistance of earth and compensatory conductors measured using current ≥200 mA with auto-zero function – meets the requirements of EN 61557-4
- Measurement of leakage current
Additional features
- Built-in GPS receiver – recording results with location coordinates
- Measurement of resistance of auxiliary electrodes RS and RH
- Measurement of interference voltage
- Measurement of interference frequency
- Measurement in the presence of interference voltage generated by power networks with frequency of 16 2/3 Hz, 50 Hz, 60 Hz, 400 Hz
- Selection of maximum measuring voltage (25 V and 50 V)
- Automatic calculation of soil resistivity in ohm-meters (Ωm) and ohm-feet (Ωft)
- Memory of 990 measurement results (10 banks of 99 cells each)
- Calibration of clamp used
- Real time clock (RTC)
- Data transmission to the computer and mobile devices
- Battery indication